Our sites are built and maintained to high standards to provide you with
the most reliable, most cost-effective service possible. The specifications
outlined below are our published standards; individual sites may vary slightly
from the Standard Specification. Power
Systems and Back Up
- 35-kilovolt primary feed established from PG&E
- Ten 2.1 megawatt Hitec CPS (Continuous Power Systems) units on-site,
identical to
power backup
systems utilized by the U.S. Department of Treasury, NATO Radar Silo
installations,
Intel, IBM and the air forces of Israel and Brazil.
- Power backup system features N+2 redundant architecture with multiple
levels
of
manual bypass for system maintenance.
- Each server room equipped with multiple static transfer switch PDU’s
(Power Distribution
Units),
redundantly fed from separate sources.
- State-of-the-art induction coupling (flywheel) system stores energy
to cover power
interruptions
or switchover to backup power. Constant-on status provides power
conditioning
for critical loads.
- Less than 1/4 cycle (0.004 second) transfer time for any power outage
or anomaly.
- Flywheel system eliminates need for legacy battery-based UPS systems,
which account
for 79%
of core power failures in large-scale data center environments.
- 60,000 gallons of fuel stored on-site for 72 hour full-load power capacity.
- Contracts in place with two fuel providers for ongoing self-generation.
- Diesel fuel fill ports at building exterior for convenient tanker access
during majorevents.
HVAC Systems
and Backup
- Six 800-ton cooling towers provide N+2 redundant cooling water capacity.
- Redundant pumps (15), heat exchangers and valving allow for uninterrupted
service at
full capacity
during any maintenance period.
- Multiple 20-ton CRAC (Computer Room Air Conditioning) units cool up
to 1,000,000
kilowatts
load in each computing area with N+2 level redundancy.
- Automated energy-saving climate and building management controls monitor
and adjust
all points
in the HVAC systems.
- Diverse loop system allows water supply & return to be established
at various points in
any direction.
- State of the art leak detectors continuously monitor computing room
areas, with
accuracy
to 12 inches.
- Capacity to cool rack/cabinet densities up to 350 watts per square foot.
- 300,000-gallon
make-up water tank provides up to 14 days of water supply
- Redundant make-up water and building water pumps provide 2N capacity
to cooling
tower’s
water supply.
- Chemical treatment stations minimize HVAC system corrosion.
Security
and Safety
- CCTV monitoring 24/7/365 by both hidden & visible CCTV systems in
all essential
perimeter
and interior areas. Remote joystick control of camera heads. All surveillance
videotape
is archived on-site.
- Designed for on-site security staff 24/7/365 with responsibility for
access control, CCTV
monitoring,
and asset protection for facility.
- Outer perimeter
walls of computing spaces are Level III resistant against bullet and
explosive
attacks.
- Card access system controls all entry points.
- Physical alarms on stairwells and exterior doors.
- Limited access by authorized personnel only beyond lobby entrance.
- Key access only to computing vaults, cages and cabinets.
- Computing areas are separated by access codes. Tenants will have access
to their
specific
locations only.
- Proprietary alarm systems within tenant spaces.
- Corridors remotely sealable from CCTV station to create “man-trap”.
- Equipment and parcels checked in at front desk.
Connectivity
- Two connection entry vaults at building property line, currently supporting
thousands of
strands of fiber-optic cable.
- Redundant cable and fiber-optic vaults guarantee room for massive network
expansion
through multiple existing duct banks.
- Diverse, redundant paths to MDF and Telco rooms.
- Telco environments with 8,000 amps of DC distribution are available
on the first floor.
- One MDF (Main Distribution Frame) room per two computing rooms, assuring
survivability
through an isolated disaster.
- POP (Point of Presence) services on-site.
- Cross Connecting services available on-site.
Intelligent Planning & Design
- Highly sophisticated Building Monitoring System operates 24/7/365 with
forensic
capabilities.
- Network-neutral connection platform located on first floor. Easy access
to multiple carrier
cross connects.
- Easy-access data center floor plates are raised 24” above cement,
with identical central
trunk architecture on each floor for shortest wire runs.
- Laser-based VESDA (Very Early Smoke Detection) combines with heat detectors
in
tightly defined zones. Fire events are quickly isolated and extinguished
without impact to
surrounding areas.
- Ceilings have pre-installed main run cable troughs for connectivity
to MDF (Main
Distribution Frame) rooms.
- Central MDF rooms are isolated from computing floor areas.